it's catit's single

D250 GC (60 Hz) Generator Set

D250 GC (60 Hz) Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Request a Quote

Maximum Rating250 ekW

Minimum Rating250 ekW

Emissions/Fuel StrategyEPA Stationary Emergency

Voltage208 to 600 Volts

Frequency60 Hz

Speed1800 rpm

Duty CycleStandby

Engine ModelCat® C9 In-line 6, 4-cycle Diesel

Bore4.4in

Stroke5.9in

Displacement538in³

Compression Ratio16.3:1

AspirationTurbocharged Air-to-Air Aftercooled

Fuel SystemHEUI

Governor TypeAdem™A4

Length - Maximum155.5in

Width - Minimum56.3in

Width - Maximum56.7in

Height - Minimum67.2in

Height - Maximum86.7in

Dry Weight - Genset (minimum)5324.2lb

Dry Weight - Genset (maximum)6735.1lb

Standard

Air cleaner - Non canister, disposable

Aftercooler core

Turbocharger

Optional

Air cleaner (Non canister disposable)

Standard

GCCP 1.2

Standard

Jacket water pump, gear driven, centrifugal

Radiator sight gauge

Blower fan and fan drive with guards

Thermostats and housing

Coolant drain valve

Radiator, package mounted

Standard

Exhaust manifold - dry

Optional

6" Muffler - 25 dBA attenuation

Flexible exhaust connection

Manifold and turbocharger guards

Standard

Fuel priming pump

Engine fuel transfer pump

Primary fuel filter w/integral water separator and secondary filter, spin on

Integral tank base, 24 hours, UL142

Standard

Factory tested to design specifications at full load conditions

Complete system designed & built at ISO 9001:2000 certified facilities

All protective devices and control functions simulated and checked

Standard

Easy access to AVR and terminals

Insulation system, Class H

Brushless, self-excited 2/3 pitch (600V uses Internal excitation (IE))

Voltage regulator (single phase sensing)

Terminal box, IP22 RHS facing, bottom cable entry

12 Leads

Standard winding protection for non-harsh environments with relative humidity ? 95%

IP23 Protection

Standard

Cat electronic governor (ADEM A4)

Standard

Oil filler and dipstick

Lubricating oil, CK-4 (10W-30)

Shallow oil pan

Oil filter, spin on

Fumes disposal to front of radiator

Oil cooler

Oil drain with valve

Standard

Includes lifting provisions and termination points for coolant and lube oil drain lines

Captive linear vibration isolators between base and engine-generator

Standard

Safety shutoff - Overspeed

Safety shutoff - High water temperature

Safety shutoff - Low oil pressure

Standard

24-volt electric starting motor

24V, 45 Amp Charging alternator

Standard

Vibration damper

Lifting eyes

Parts book

Optional

CSA Certification

Extended Service Coverage

Generator test report

UL2200 Certification

Optional

Integral tank base, 24 hours, UL142

Audio & visual fuel alarm (@90% fuel level)

Wide Base - Skid

Fuel tank pill pipe & lockable cap

Optional

400A LS/I

600A LS/I

1200A LSI

600A LSI

1200A LS/I

Auxiliary contacts

400A LSI

800A LSI

800A LS/I

Optional

Twist release, Red button emergency stop

Product link remote monitoring hardware

16 -light NFPA 99/110 Annunciator

Volt free contacts

Ground fault relay

20A GFCI (Ground Fault Circuit Interrupter)

Audible alarm Gp

100A Load center

Optional

E-Stop

AC & DC Source lights

Sound attenuated Level 2 enclosure (White)

Optional

Permanent magnet excitation (PMG) generator

Space heater

Optional

Standard battery set: 1000 CCA, 90 amp/hr.

Battery charger (UL Certified)

Jacket water heater