Standby Rating1400/1250 kVA

Prime Power Rating1275/1150 kVA

Emissions/Fuel StrategyLow Fuel Consumption

Voltage380 to 415 Volts

Frequency50 Hz

Speed1500 rpm

Duty CycleStandby, Mission Critical, Prime, Continuous

Maximum Rating1400 kVA

Minimum Rating1000 kVA

Engine Model3512 TA, V-12, 4-Stroke Water-Cooled Diesel

Bore6.69in

Stroke7.48in

Displacement3161.03in³

Compression Ratio13.5:1

AspirationTA

Fuel SystemDirect Unit Injection

Governor TypeWoodward

Length - Minimum202.7in

Length - Maximum206.6in

Width - Maximum77.8in

Height - Maximum93.2in

Dry Weight - Genset (minimum)22650lb

Dry Weight - Genset (maximum)23170lb

Estándar

Air cleaner; single element canister type with service indicator

Opcional

Remote air inlet adaptors

Air Inlet protection

Dual Element air cleaners

Estándar

EMCP4.2B controls including: Emergency stop pushbutton

RPM

Engine cool-down timer

EMCP4.2B controller including:

Accessory module data link

4 programmable relay outputs (Form A)

Communications:

Volts (L-L & L-N)

Over / under frequency (81 o / u)

Text alarm / event descriptions

Auto / start / stop control

Speed adjust

kVA (per phase, average & percent)

Overcurrent (50 / 51)

Alarm acknowledge

Environmental sealed front face

6 programmable digital inputs

Oil pressure (psi, kPa or bar)

Amps (per phase & average)

Generator phase sequence

2 Programmable digital outputs

Low coolant temperature

Controls:

Serial annunciator module data link

Reverse Power (kW) (32)

Lamp test

Coolant temperature

Engine cycle crank

kVAr-hr (total)

2 Programmable relay outputs (Form C)

Generator mounted - rear facing

24-volt DC operation

kVAr (per phase, average & percent)

Warning/shutdown with common LED indication of shutdowns for:

kW (per phase, average & percent)

Reverse Reactive Power (kVAr) (32RV)

Programmable protective relaying functions:

Digital indication for:

High coolant temperature

Low oil pressure

Overspeed

Over / under voltage (27 / 59)

Customer data link (Modbus RTU)

DC volts

Operating hours

Low coolant level

kW-hr (total)

Frequency (Hz)

Emergency stop

Power Factor (per phase & average)

Failure to start (overcrank)

True RMS AC metering, 3-phase, +/-2% accuracy

Opcional

Auxiliary Boxes

Customer connection mounting locations

Ground (Automatically selected)

Vandle proof panel door

Customer Interface Options

Mounting Group - External Box Clips

Remote speed adjust

Generator Temperature Monitoring

Governors

Annunciator Modules

Local PC monitoring

Estándar

JWAC

Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)

Radiator fan and fan drive

Fan and belt guards

Coolant drain line with valve

Coolant level sensors. (Not included with packages without radiator)

Opcional

Water level switch gauges

Heat exchangers

Optional radiator arrangements

Estándar

Dry Exhaust Manifold

Flanged faced outlet(s)

Opcional

Through-wall installation kit

Muffler mounting kits

Mufflers

Flexible fittings

Estándar

Fuel cooler; not included with packages without radiator

Flexible fuel lines - shipped loose

Fuel priming pump

Secondary fuel filters

Opcional

Primary fuel filter

Estándar

Generator set packages include: Regulator (CDVR)

6 Lead

Min / max exciter limiter

LV:

Reactive droop capability

Random wound

Exciter diode monitor

KVAR/PF modes

NEMA Class H insulation

50 Hz models: IEC standard hole pattern

Caterpillar's Digital Voltage Regulator (CDVR) includes:

Note: 1800 frames are form wound, permanent magnet, with winding temp detectors

Busbar connections, top center mounted, top cable entry

Internal Excitation

Winding temperature detectors

Class H temperature rise at 40C ambient (125C prime/150C standby)

3 Phase brushless, salient pole

3 Phase voltage sensing

RFI suppression

Opcional

380 / 400 / 415 Volts @ 50 Hz, 3 phase, form wound, permanent magnet, No. of leads = 6, pitch= 0.6667

380/400/415volts @ 50 Hz, 3 phase, random wound, permanent magnet, No. of leads = 6, pitch= 0.6667

Generator conversion

380/400/415volts @ 50 Hz, 3 phase, random wound, internal excitation, No. of leads = 6, pitch= 0.6667

Space heater

Estándar

Woodward 2301A isochronous governor

Estándar

Oil drain lines and valve

Gear type lube oil pump

Fumes disposal

Oil filter, filler and dipstick

Lubricating oil

Integral lube oil cooler

Opcional

Electric prelube pumps

Oil level Reg-1 shallow pan

Manual prelube sump pumps

Estándar

Rubber anti-vibration mounts (shipped loose)

Rails - engine/generator/radiator mounting

Opcional

Spring-type vibration isolator

IBC vibration isolators

Estándar

24 Volt electric starting motor

Battery and battery rack w/cables

Interruptor de desconexión de la batería

Estándar

Paint - Caterpillar Yellow with high gloss black rails & radiator

SAE Standard Rotation

RH Service

Flywheel and Flywheel housing - SAE No. 00

Opcional

Engine barring group

Opcional

EMAX circuit breakers

Center posts busbars

EMAX breakers connections

Breaker harnesses

2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated circuit breakers

Controls packaging - Enclosures

Cable entry options

2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated circuit breakers

Optional busbar power connections

Busbar connections

Opcional

EU declaration of conformity

Eurasian conformity (EAC) mark

European directive genset, DoI (Declaration of Incorporation)

European Union Certification

Opcional

Pyrometer and thermocouples

Opcional

Explosion relief valve

Opcional

Neutral grounding connection

IBC seismic certifications

Neutral ground-LV

PGS test report @ 1.0 power factor

PGS test report @ 0.8 power factor

Opcional

Ether starting aid

24 Volt dual electric starting motor

20 Amp battery charger

Oversize battery set

Jacket water heaters

10 Amp battery chargers

CONTACTO

SOLICITAR PRESUPUESTO

Rellene este formulario para obtener un presupuesto sobre el equipo que le interesa.

    *Si desea dejar de recibir comunicaciones en el futuro, puede darse de baja enviando un mensaje de texto a STOP, QUIT, END, REVOKE, OPT-OUT, CANCEL, o UNSUBSCRIBE. Pueden aplicarse tarifas de mensajes y datos en función del plan de su operador de telefonía móvil. Al optar por recibir comunicaciones SMS de Blanchard Machinery, acepta recibir mensajes de texto recurrentes sobre actualizaciones de cuenta, notificaciones de pedidos, notificaciones de entrega y asistencia general.

    Este sitio está protegido por reCAPTCHA y se aplican la Política de privacidad y las Condiciones del servicio de Google.

    Lo que obtiene: Una llamada telefónica de un representante o agente. Una estimación del coste de su máquina o del proyecto. Una consulta en persona si es necesario.