it's catit's single

CAT® EMCP 4.1 Control Panel

CAT® EMCP 4.1 Control Panel

The Cat® EMCP 4 Control Panel provides all of the controls and system indicators in one easy to access interface.

Request a Quote

Standard

Auto / Start / Stop control

Remote start / stop

Speed and voltage adjust

Engine Cooldown Timer

Local and remote emergency stop

Engine Cycle Crank

Standard

A 33 x 132 pixel, 3.8 inch, graphical display denotes text alarm/event descriptions, set points, engine and generator monitoring and is visible in all lighting conditions

Standard

Voltage (L-L, L-N)

Current (Phase)

Average Volt, Amp, Frequency

Standard

Over/Under voltage (27/59)

Over/Under frequency (81/OU)

Generator phase sequence

Standard

Engine speed (RPM)

Battery voltage

Oil pressure

Oil Temperature

Coolant temperature

Multiple Language Support

Crank attempt and successful start counter

Run hours

Standard

Low engine oil pressure (alarm)

High engine oil temp (alarm and shutdown)

High coolant temp (alarm and shutdown)

Low coolant temp (alarm)

Low coolant level (alarm)

Overcrank

Overspeed

Control switch not in auto (alarm)

Low, high, and weak battery voltage

Standard

Primary CAN data link

Standard

Six programmable form A dry contacts

Two dedicated analog inputs

One programmable analog input

Two dedicated digital inputs

Six programmable digital inputs

Standard

Arabic, Bulgarian, Chinese, Czech, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Icelandic, Italian, Latvian, Lithuanian, Japanese, Norwgian, Polish, Portguese, Romanian, Russian, Slovak, Slovene, Spanish, Swedish & Turkish

Standard

Control module operating temperature: -40°C to 70°C

Display operating temperature: -20°C to 70°C

Humidity: 100% condensing 30°C to 60°C

Storage temperature: -40°C to 85°C

Vibration: Random profile, 24-1000 Hz, 4.3G ms