it's catit's single

EMCP 4.2 Generator Set Controller

EMCP 4.2 Generator Set Controller

The Cat® EMCP 4 Control Panel provides all of the controls and system indicators in one easy to access interface.

Request a Quote

Standard

Auto / Start / Stop control

Remote start / stop

Speed and voltage adjust

Engine Cooldown Timer

Local and remote emergency stop

Engine Cycle Crank

Programmable Cycle Timer

Standard

A 33 x 132 pixel, 3.8 inch, graphical display denotes text alarm/event descriptions, set points, engine and generator monitoring and is visible in all lighting conditions

Standard

Voltage (L-L, L-N)

Current (Phase)

Average Volt, Amp, Frequency

kW, kVAr, kVA (Average, Phase, %)

Power Factor (Average, Phase)

kW-hr, kVAr-hr (total)

Optional

Excitation voltage and current (with CDVR)

Generator stator and bearing temp (with optional module)

Standard

Over/Under voltage (27/59)

Over/Under frequency (81/OU)

Generator phase sequence

Overcurrent (50/51)

Reverse Power (kW)(32)

Reverse Reactive Power (kVAr) (32RV)

Standard

Engine speed (RPM)

Battery voltage

Oil pressure

Oil Temperature

Coolant temperature

Multiple Language Support

Crank attempt and successful start counter

Run hours

Enhanced engine monitoring (with electronic engines)

Standard

Low engine oil pressure (alarm)

High engine oil temp (alarm and shutdown)

High coolant temp (alarm and shutdown)

Low coolant temp (alarm)

Low coolant level (alarm)

Overcrank

Overspeed

Control switch not in auto (alarm)

Low, high, and weak battery voltage

Standard

Primary and accessory CAN data links

RS-485 annunciator data link

Modbus RTU (RS-485 Half duplex)

Standard

Six programmable form A dry contacts

Two programmable form C dry contacts

Two digital outputs

Two dedicated analog inputs

One programmable analog input

Two dedicated digital inputs

Six programmable digital inputs

Standard

Arabic, Bulgarian, Chinese, Czech, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Icelandic, Italian, Latvian, Lithuanian, Japanese, Norwgian, Polish, Portguese, Romanian, Russian, Slovak, Slovene, Spanish, Swedish & Turkish

Standard

Control module operating temperature: -40°C to 70°C

Display operating temperature: -20°C to 70°C

Humidity: 100% condensing 30°C to 60°C

Storage temperature: -40°C to 85°C

Vibration: Random profile, 24-1000 Hz, 4.3G ms

Optional

The EMCP 4 CAN Annunciator serves to display genset system alarm conditions and status indications.The annunciator has been designed for use on the accessory communication network and may be used in either local (package mounted) or remote (up to 800 feet) application.

A maximum of three annunciators may be used with a single EMCP 4.2

Optional

The EMCP 4 RS-485 Annunciator serves to display genset system alarm conditions and status indications.The annunciator has been designed for use on the long distance annunciator datalink and is used for remote (up to 4000 feet) application.

Optional

The EMCP 4 remote monitoring software package is a PC based program which allows the user tomonitor and control a generator set, and is capable of running on a Windows based operating system.The remote monitoring software allows the user to configure data monitoring and data acquisitionprocesses for monitoring, graphing, and logging of genset data.

Optional

The Digital Input/Output (DI/O) module serves to provide expandable Input and Output capability of the EMCP 4 and is capable of reading 12 digitalinputs and setting 8 relay outputs. The DI/Omodule has been designed for use on the accessoryCommunication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.

A maximum of four DI/O modules may be used with a single EMCP 4.2.

Optional

The RTD module serves to provide expandable generator temperature monitoring capability of the EMCP 4 and is capable of reading up to eight type 2-wire, 3-wire and 4-wire RTD inputs. The RTD Module has been designed for use on the Accessory Communication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.

A maximum of one RTD Module may be used with a single EMCP 4.2.

Optional

The thermocouple module serves to provide expandable engine and generator temperature monitoring capability of the EMCP 4 and iscapable of reading up to twenty Type J or K thermocouple inputs. The thermocouple module has been designed for use on the accessory communication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.

A maximum of one thermocouple module may be used with a single EMCP 4.2 on each datalink.

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.