Rating Range120 to 600V, single phase and three phase @ 50/60 Hz
Transfer TypeSwitch application dependent
Switch TypeSwitch application dependent
Input Control Voltage65 to 145 Vac 50/60 hZ
Voltage Measurements of UtilitySource 1 VAB Source 2 VAB
Source 1 VAC Source 2 VBC
Source 1 VCA Source 2 VCA
Voltage Measurement Range0 to 790 VAC rms (50/60 Hz)
Voltage Measurement Accuracy+/-2% of nominal input voltage
Frequency Measurements OfSource 1 and Source 2
Frequency Measurement Range40 Hz to 70 Hz
Frequency Measurement Accuracy+/- 0.1 Hz
Undervoltage Dropout50% to 90% of nominal voltage
Undervoltage Pickup(Dropout +2%) to 99% of the nominal system voltage
Underfrequency Dropout Range90 to 97% of the nominal system frequency
Underfrequency Pickup Range(Dropout +1 Hz) to 99% of the nominal system frequency
Overfrequency Dropout Range103 to 110% of the nominal system frequency
Overfrequency Pickup Range101% to (dropout - 1 Hz) of the nominal system frequency
Operating Temperature Range-20 to 70 degree C (-4 to +158 degree F)
Storage Temperature Range-30 to 85 degree C (-22 to +185 degree F)
Operating Humidity0 to 95% relative humidity (noncondensing)
Operating EnvironmentResistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
Generator Start Relay5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
K1, K2 Relays
10A, 1-3 hp @ 250 Vac
10A@30 Vdc
Applicable TestingUL-recognized component
Meets intent of UL 991 & UL 1008
Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
Applicable Testing Continued1000-4-5, 1000-4-6, 1000-4-11
CISPR 11, Class A
FCC Part 15, Class A
CSS 22.2-178
Enclosure CompatibilityNEMA 1, NEMA 3R and NEMA 12
UV-resistant ATC-300+ faceplate