it's catit's single

D60 GC Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Request a Quote

Maximum Rating60 ekW

Minimum Rating60 ekW

Emissions/Fuel StrategyU.S. EPA Cert., Tier 3

Voltage208 to 600 Volts

Frequency60 Hz

Speed1800 rpm

Duty CycleStandby

Engine ModelC4.4, In-line 4, 4-cycle diesel

Bore4.1in

Stroke5in

Displacement269in

Compression Ratio16.7:1

AspirationTurbocharged

Fuel SystemElectronic (adjustable)

Governor TypeMechanical, ADEM™A4

Length - Maximum77.2in

Width - Maximum43.3in

Height - Maximum48in

Dry Weight - Genset (maximum)2054lb

Standard

IBC seismic and wind Certifications

Optional

IBC seismic and wind Certifications

Standard

Air cleaner

Cartridge type air filter

Optional

Cartridge type air filter

Standard

Breakers (100% UL rated)

3-Pole 100% rated

Second circuit breaker box

Power terminal strip

Optional

Breakers (100% UL rated)

3-Pole 100% rated

Second circuit breaker box

Power terminal strip

Standard

NFPA battery charger UL10A 120VAC

Optional

NFPA battery charger UL10A 120VAC

Standard

GCCP 1.2 Control panel

Standard

Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose

Optional

10, 25 and 35 dBA silencer systems

Overhead silencer mounting kit

Standard

Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank

Optional

Emergency vent pipe

Tank riser

5 Gallon spill containment

209 and 394 gallon sub-base fuel tanks

5 Gallon fill containment

Standard

WSS1 Low coolant level shut down

FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected

NFPA110 bundle includes:

WCA1 Low coolant temperature alarm

A Coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application

PBC10NU NFPA battery charger

Oil temperature gauge and sender

PAA1 Panel mounted audible alarm

Ground fault relay

Remote E-stop button

Remote annunciator module

Audible alarm

Volt free contacts genset run and common alarm

Discrete I/O module

Overload shutdown via breaker

Low coolant temperature alarm

Protective devices:

Fuel level reading

Low coolant level shutdown

Optional

NFPA110 bundle includes: FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low coolant level shut down - WCA1 Low coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA battery charger - A Coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application

Ground fault relay

Remote E-stop button

Volt free contacts genset run and common alarm

Oil temperature gauge and sender

Audible alarm

Remote annunciator module

Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker

Discrete I/O module

Standard

Coolant drain line with valve

Fan drive, battery charging alternator drive

Caterpillar extended life coolant

Radiator and cooling fan with guards

Radiator stone guard

Optional

Radiator transition flange

Standard

12 Leads

Standard

Mechanical and electrical governing system - model dependent

Standard

Oil drain line with valve

Lubricating oil

Standard

Engine and alternator pre-paint, Caterpillar yellow

Standard

Batteries

24V battery with rack and cables

Optional

R Frame auxilliary winding

Optional

Sound attenuated enclosure, Level 1

External emergency stop

Sound attenuated Level 2 Enclosure (White)

Panel viewing window

Optional

Battery heater

Jacket water heater

Coolant heater

Anti-condensation heater

Wiring for canopy space heater

Lube oil sump heater

Optional

Permanent magnet excitation (PMG) generator

Cat Alternator

Optional

Seismic vibration isolators

Optional

4 Hour factory test

Generator test report

PGS Test report @ 0.8 power factor

PGS Test report @ 1.0 power factor

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.