it's catit's single

Cat® 3412C Fire Pump

Cat® 3412C Fire Pump

Cat® 3412C Industrial Diesel Fire Pump Engines, with ratings: 476-551 kW (638-739 hp) @ 1750-2100 rpm, are non-certified and are available for global non-regulated areas. They are not FM Approved and not UL Listed. Starting on demand is a must for a fire pump engine – always. Cat® fire pump engines have a reputation for reliable starts and long efficient service. The Cat line of fire engine pumps covers a wide range of installations.

Request a Quote

Maximum Power739HP

Rated Speed1750-2100 rpm

Minimum Power638HP

EmissionsNon-Certified. Available for global non-regulated areas. Not FM Approved, Not UL Listed

Engine ConfigurationV-12, 4-Stroke-Cycle Diesel

Bore5.4in

Stroke6in

Displacement1648in³

Compression Ratio14.5:1

AspirationTurbocharged Aftercooled (TA)

Rotation from Flywheel EndCounterclockwise

Aftertreatment-

Length78.7in

Height55.6in

Weight - Net Dry - Basic Operating Engine Without Optional Attachments5686lb

Standard

Air cleaner, regular duty with service indicators

Turbocharged

Standard

Thermostats and housing

Jacket water pump, centrifugal

Heat exchanger installed

Expansion tank

Standard

Charging alternator 24 volt, 35 amp

Governor control

Hydra-mechanical governor

Standard

Exhaust manifold

Exhaust elbow, dry. 203 mm (8 in) on all Turbocharged engines and Turbocharged Aftercooled with wet exhaust. 152 mm (6 in) on Turbocharged Aftercooled with dry manifolds.

Standard

SAE No. 0 flywheel

SAE No. 0 flywheel housing

SAE standard rotation

Standard

Fuel filter

Fuel transfer pump

Primary fuel filter

Fuel priming pump

Standard

Instrument panel, LH

Engine oil pressure gauge

Fuel pressure gauge

Water temperature gauge

Tachometer

Standard

Crankcase breather, top mounted

Oil cooler

Oil filler in valve cover and dipstick, both RH

Lube oil filter

Rear sump oil pan

Standard

Supports

Standard

Power take-off (PTO) flywheel stub shaft

Standard

Stop-Start System, automatic (compatible with NFPA 20 requirements, able to be energized from either of two battery sources and capable of manual starter actuation)

Standard

24 volt, LH electric starting motor

Jacket water heater (6 kW, 240-480 volt)

Standard

Paint: Firepump Red

Vibration damper and guard

Lifting eyes

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.