Rating1900 ekW (2375 kVA) Continuous

Frequency50/60 Hz

Voltage400/480 V

EngineCat G3516H

FuelNatural Gas

Width - Without Chassis96in

Height - Without Chassis114in

Length - Without Chassis480in

Weight - Without Chassis, With Lube Oil and Coolant77780lb

Standard

G3516H, V16, 4-stroke-cycle, gas engine. Operates on 24.10 to 93.95 MJ/Nm3 (615 to 2386 btu/ft3) dry pipeline natural gas. Turbocharged Separate Circuit Aftercooled

Standard

Double bearing SR5 1866 Frame, brushless, form wound, 12-lead design, permanent magnet excited, thouree-phase, with Cat IVR, Class H insulation operating at Class F temperature. Stator and Bearing temperature monitoring and anti-condensation space heaters

Standard

40' ISO high cube container, 9-high stack CSC certified. Sound attenuated 79 dB(A) @ 7 m (23 ft) Sound attenuated air intake louvers and 2lockable personnel doors with panic release LH and RH engine service doors integrated intocontainer side walls 3” ANSI flange customer fuel connection

Standard

Standard cooling provides 40⁰C (104⁰F) ambient capability with 500mg/Nm3 NOx at 100% Continuous rating before derate, @ 500m

Standard

On Package EMCP 4.3 Control Panel System Offers engine and generator monitoring and protection, voltage regulation with Cat IVRimproves transient response performance. Controls provide auto paralleling AGC-4 controller, load sharing, VFD control, and primary generator protection for greater versatility, package utilization and monitoring.

Standard

Provides for single unit stand-alone operation,island mode paralleling and load sharing withother power modules, and single unit-to-utilitymode paralleling for base load control

Standard

Oil pan-mounted oil level regulator and 114 L (30 gal) oil tank Low level annunciation

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.