3412C | 900 kVA 50Hz Generator Set

3412C | 900 kVA 50Hz Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Request a Quote

Maximum Rating680 kVA

Minimum Rating680 kVA

Emissions/Fuel StrategyLow Fuel Consumption

Voltage380 to 415 Volts

Frequency50 Hz

Speed1500 rpm

Duty CycleStandby, Prime

Engine Model3412C TA, V-12, 4-Stroke Water-Cooled Diesel

Bore5.4in

Stroke6in

Displacement1648.86in³

Compression Ratio13:01

AspirationTurbocharged, Air to Air Aftercooled

Fuel SystemPump and Lines

Governor TypeADEM™ A5

Length - Maximum162.4in

Width - Minimum75in

Width - Maximum78.3in

Height - Maximum75in

Dry Weight - Genset (minimum)12039lb

Dry Weight - Genset (maximum)13030lb

Standard

Air cleaner, single element canister type with service indicator

Optional

Dual element air cleaners

Heavy duty air cleaners

Open element air cleaners

Standard

GCCP Control panel

Emergency stop pushbutton

Overspeed

Text alarm/event descriptions

Low coolant temperature

Frequency (Hz)

Overcurrent (50 / 51)

4 programmable relay outputs (Form A)

Volts (L-L & L-N)

Programmable protective relaying functions:

Warning/shutdownn with common LED indication of shutdowns for:

24 Volt DC operation

Over/under voltage (27 / 59)

Engine cycle crank

Over/under frequency (81 o/u)

Remote CAN annunciator

Remote Serial annunciator

kW (per phase, average & percent)

Digital I/O module

Failure to start (overcrank)

Low oil pressure

Low coolant level

Run/auto/ stop/control

6 programmable digital inputs

Accessory module data link

Features include:

Compatible with the following optional modules:

Serial annunciator module data link

kVA (per phase, average & percent)

Voltage adjust

RPM

Generator temperature monitoring module

kVAr (per phase, average & percent)

2 Programmable relay outputs (Form C)

DC volts

Communications

Local annunciator

Power factor (per phase & average)

Speed adjust

Emergency stop

Reverse power (kW) (32)

coolant temperature

Digital indication for:

Reverse reactive power (kVAr) (32RV)

Customer data link (Modbus RTU)

kW-hr (total)

Amps (per phase & average)

High coolant temperature

Generator phase sequence

Oil pressure (psi, kPa or bar)

Operating hours

2 Programmable digital outputs

Environmental sealed front face

Optional

Ground fault relay

Vandal proof panel door

First local annunicators

Common alarm/shutdown relay

Remote custom annunicator

GCCP Control panel

Generator running VFC

GCCP Control panel

Local discrete I/O package

Generator temperature monitoring package

Standard

Fan and belt guards

Radiator with guard (Sized for 50 degrees C)

Coolant drain line with valve, piped to edge of base

Coolant level shutdown

Caterpillar extended life coolant

Optional

Radiator duct flange

Jacket water heaters

Standard

Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose

Optional

Manifold and turbocharger guards

Through wall installation kit

Elbow kit

Mufflers

Standard

Primary and Secondary fuel filters

Water seperator

Flexible fuel lines terminated on base

Fuel priming pump

Standard

3-phase sensing

Busbar termination

SR4B self excited

2:1 Volts/Hz

Class F temperature rise

12 Leads

Class H insulation

Reactive droop

VR6 voltage regulator

Optional

Permanent magnet excitation (PMG)

Space heater

Digital voltage regulator

Oversize and premium generators

Standard

Cat electronic governor

Optional

Electronic load share

Standard

Oil drain line with valve, piped to edge of base

Oil filter

Fumes disposal, piped to front of radiator

Lubricating oil

Optional

Manual sump pump

Standard

Base, formed steel with linear vibration isolators between base and engine-generator

Optional

Fuel tank base (1200 ltr)

Standard

Fuel shutoff solenoid

45 amp Charging alternator

Battery with rack, cables

24 volt starting motor

Optional

1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip

1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip

Optional

Eurasian Conformity (EAC) mark

Optional

PGS Test report @ 0.8 power factor

PGS Test report @ 1.0 power factor

Optional

Battery disconnect switch

Heavy duty starting system

Battery chargers

Oversize batteries

CONTACT US

REQUEST A QUOTE

Complete this form to get a quote on the equipment you are interested in.

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

    What You Get: A phone call from a rep or agent. A cost estimate for your machine or the project. An in-person consultation if necessary.